Sku: 1127550826

Μετρητής Uni-T UT526 Multifunction Meter for Electricians

207,53 €
TBI Bank
Up to 36 instalments by credit card x 6,48€ / month 
Product Availability
call us
Need help?

Συμπλήρωσε τα στοιχεία σου για να σε καλέσουμε άμεσα.

Call us now!
Shop now
Methods of Pickup/Shipment
  • Pickup from the store:
    El. Ave. Venizelou 73 (formerly Theseos), Kallithea
  • Pick up from a BoxNow machine:
    With BoxNow you can pick up your parcel from an Automatic Pickup Machine that is near you at all hours of the day 24/7. Possibility of cash on delivery with an additional fee of €1
  • Shipping to your location (Calculate shipping):

Detailed Description

The Uni-T UT526 Multifunction Electrical Meter is a versatile and reliable tool designed for electricians and professionals in the electrical testing and measurement field. This multifunctional meter is equipped with a wide range of features that make it an essential device for various electrical applications.

Key Features

  • Display Count: The meter features a large quality LCD display that can count up to 10,000 readings, providing clear and accurate data.
  • Manual Range: The UT526 allows for manual range selection, enabling users to adjust the measurement settings according to their specific needs.
  • Phase Switch (RCD): The meter includes a phase switch with settings of 0° and 180°, facilitating the testing of RCD (Residual Current Device) status.
  • Low Battery Indication: The device is equipped with a low battery indication feature, ensuring that users are aware when the battery needs to be replaced.
  • Auto AC/DC Voltage Identification: The UT526 can automatically identify AC or DC voltage, providing quick and accurate measurements.
  • Red Warning Lights: The meter features red warning lights to alert users of potential issues or errors during testing.

Technical Specifications

  • Insulation Resistance (Ω): Test Voltages: 250V, 500V, and 1000V. Measurement Range: 250V: 0.05MΩ to 200MΩ, 500V: 0.05MΩ to 300MΩ, 1000V: 0.05MΩ to 500MΩ.
  • Load Current: 250V (R=250kΩ): 1mA, 500V (R=500kΩ): 1mA, 1000V (R=1MΩ): 1mA.
  • Short Circuit Current: Less than 2mA.
  • RCD Testing: Operating Voltage: 220V (45Hz to 65Hz). Test Current: 10mA, 30mA, 100mA, and 300mA. Trip Time: ranges from 0ms to 2000ms depending on the configuration.
  • Low Resistance Continuity: Range: 0Ω to 2000Ω. Test Voltage: Approximately 5V. Test Current: Greater than 200mA (R < 2Ω).

Specifications

  • Insulation Resistance Test Voltages
    • 250V, 500V, 1000V
  • Insulation Resistance Measurement Range 250V
    • 0.05MΩ to 200MΩ
  • Insulation Resistance Measurement Range 500V
    • 0.05MΩ to 300MΩ
  • Insulation Resistance Measurement Range 1000V
    • 0.05MΩ to 500MΩ
  • Load Current 250V
    • 1mA (R=250kΩ)
  • Load Current 500V
    • 1mA (R=500kΩ)
  • Load Current 1000V
    • 1mA (R=1MΩ)
  • Short Circuit Current
    • < 2mA
  • RCD Operating Voltage
    • 220V (45Hz to 65Hz)
  • RCD Test Current
    • 10mA, 30mA, 100mA, 300mA
  • RCD Trip Time
    • 0ms to 2000ms
  • Low Resistance Continuity Range
    • 0Ω to 2000Ω
  • Low Resistance Continuity Test Voltage
    • ~5V
  • Low Resistance Continuity Test Current
    • > 200mA (R < 2Ω)